The federal thresholds
| Category | Threshold | Rule |
|---|---|---|
| Extremely hazardous substance (EHS) | 500 lb or the threshold planning quantity, whichever is lower | 370.10(a)(1) |
| Any other hazardous chemical with an SDS | 10,000 lb | 370.10(a)(2)(i) |
| Gasoline at a retail gas station, underground tanks in full compliance all year | 75,000 gallons, all grades combined | 370.10(a)(2)(ii) |
| Diesel at a retail gas station, underground tanks in full compliance all year | 100,000 gallons, all grades combined | 370.10(a)(2)(iii) |
| Any hazardous chemical, when the SERC, LEPC or fire department requests Tier II information | Zero | 370.10(b) |
A retail gas station under the rule is a retail facility that sells gasoline or diesel principally to the public for motor vehicles. A warehouse fueling its own yard trucks or fleet is not one, so its gasoline and diesel use the 10,000 lb threshold.
Common warehouse chemicals
| Chemical | EHS? | Threshold planning quantity | Tier II threshold |
|---|---|---|---|
| Sulfuric acid, CAS 7664-93-9 (lead acid batteries) | Yes | 1,000 lb | 500 lb |
| Anhydrous ammonia, CAS 7664-41-7 (refrigeration) | Yes | 500 lb | 500 lb |
| Chlorine, CAS 7782-50-5 (water treatment) | Yes | 100 lb | 100 lb |
| Lead (lead acid batteries) | No | None | 10,000 lb |
| Diesel fuel | No | None | 10,000 lb |
| Propane | No | None | 10,000 lb |
| Gasoline (non-retail) | No | None | 10,000 lb |
Run your own amounts through the threshold checker, which also converts gallons to pounds.
At any one time
Every threshold is measured as the amount present at the facility at any one time during the calendar year. It is the peak day, not the yearly total that moved through the building. A site that receives 30,000 lb of diesel over a year but never holds more than 6,000 lb at once is under the 10,000 lb line. A site with 12 large forklift batteries on site on one day is over the 500 lb acid line for that year.
The threshold applies to the whole facility. For an extremely hazardous substance you add the amount in every container and mixture on site, including the acid in each battery. The aggregation guide covers the mixture rules.
States can set lower thresholds
EPA's guidance says states have always had the flexibility to add chemicals, set lower thresholds and ask for more information than the federal form. Several do.
| State | State rule | Source |
|---|---|---|
| California | Hazardous materials business plan at 55 gallons of a liquid, 500 lb of a solid or 200 cubic feet of compressed gas | LAFD CUPA |
| Delaware | Hazardous chemicals at 55 gallons or 500 lb, whichever is lower; building heating fuel at 10,000 lb | DNREC instructions |
| Louisiana | 500 lb, unless an EHS threshold is lower | Louisiana State Police FAQ |
| New Jersey | For covered NAICS codes, lead or sulfuric acid in forklift and backup batteries reportable at 500 lb in aggregate | NJDEP CRTK FAQ |
| Missouri | Explosives or blasting agents over 100 lb on hand at any one time | RSMo 292.606 |
| Oregon | State hazardous substance survey at 500 lb, 500 gallons or 500 cubic feet for most hazardous substances, with far lower amounts for highly toxic substances and explosives | OAR 837-085 |
| Hawaii | Facilities with 10,000 lb or more of lithium-ion batteries designated for reporting from December 12, 2025 | Hawaii HEER guideline |
Each state page lists the extra rules we found on the state's own pages.
Common questions
Is the threshold per container or per site?
Per facility. Compare the total on site on the peak day with the threshold. Extremely hazardous substances are added up across every container and mixture.
Do I count a chemical that is under 1% of a mixture?
No. Under 40 CFR 370.14(c) you do not count a component at 1% or less, or 0.1% or less for a carcinogen.
Does the 75,000 gallon gasoline threshold apply to my fleet tank?
No. It applies only to retail gas stations selling principally to the public, with underground tanks in compliance all year.
We build the battery and chemical inventory, check every threshold and file in your state's system. $950 a site per year, $750 a site from the third site. State fees extra.
Get a quote- 40 CFR 370.10, thresholds (eCFR)
- 40 CFR 370.14, mixtures (eCFR)
- 40 CFR part 355, Appendix A (eCFR)
- EPA, EPCRA sections 311 and 312
- EPA, Lithium-ion batteries and EPCRA 311 and 312
- Los Angeles Fire Department CUPA, hazardous materials business plan
- Delaware DNREC, Tier II online reporting instructions
- Louisiana State Police, Right-to-Know FAQ
- New Jersey DEP, Community Right to Know FAQ
- Missouri Revised Statutes 292.606
- Hawaii HEER, summary implementation guideline, reporting year 2025
- Oregon Administrative Rules, chapter 837 division 85, hazardous substance reporting