Warehouse Filings

When does diesel in a warehouse need a Tier II report?

Diesel is reportable on Tier II when the total stored on site reaches 10,000 lb at any one time, counting generator, fire pump and fueling tanks together. That is roughly 1,300 to 1,470 gallons, depending on the specific gravity on your SDS. The 100,000 gallon figure applies only to retail gas stations.

Reviewed November 2026 · 10 sources listed at the end

Key facts
Threshold10,000 lb on site at any one time, all tanks together (40 CFR 370.10(a)(2)(i))
In gallonsRoughly 1,300 to 1,470 gallons, depending on specific gravity
ConversionGallons × specific gravity × 8.3 (TCEQ weight converter)
100,000 gallon figureRetail gas stations only, for compliant underground tanks
DueMarch 1, for the previous calendar year

The threshold for warehouse fuel

Diesel and gasoline are hazardous chemicals with safety data sheets, and neither is on EPA's list of extremely hazardous substances. At a warehouse both use the general 10,000 lb threshold in 40 CFR 370.10(a)(2)(i). The higher thresholds in the rule, 75,000 gallons of gasoline and 100,000 gallons of diesel, apply only at retail gas stations that sell fuel principally to the public, and only for underground tanks in compliance with the UST rules all year. A warehouse fueling its own yard trucks or fleet does not qualify.

Add up every tank

The test is the total on site at any one time. Add the diesel in:

  • emergency generator day tanks and base tanks
  • fire pump engine tanks
  • yard truck or fleet fueling tanks
  • drums and totes kept for equipment

Use the highest day of the year, which is often just after a fuel delivery.

Gallons to pounds

Tanks are measured in gallons and the threshold is in pounds. TCEQ's Tier II weight converter multiplies gallons by the specific gravity from the safety data sheet and by 8.3. One diesel SDS, from Vitol, lists a specific gravity of 0.82 to 0.93 at 60 °F, so the gallons needed to reach 10,000 lb fall in a range.

Arithmetic using the TCEQ method (gallons × specific gravity × 8.3) across the specific gravity range on the Vitol Diesel Fuels SDS. Use the figure on your own fuel's SDS.
Specific gravityPounds per gallonGallons at 10,000 lbPounds in 1,000 gallons
0.826.81 lb1,469 gal6,806 lb
0.857.06 lb1,417 gal7,055 lb
0.887.30 lb1,369 gal7,304 lb
0.937.72 lb1,296 gal7,719 lb

So a site storing roughly 1,300 to 1,470 gallons of diesel or more on one day is at the 10,000 lb line, depending on the fuel. A single large generator base tank can be enough on its own.

Gasoline and other fuels

Non-retail gasoline also uses 10,000 lb. If you keep both diesel and gasoline, they are separate chemicals, each compared with its own threshold. Propane has its own page: propane forklifts and Tier II.

What goes on the report

For a reportable fuel, the Tier II entry gives the product name and CAS number as shown on the SDS, the hazard categories, the maximum and average daily amounts as range codes, days on site, storage type such as above-ground tank, storage conditions, and the tank location (40 CFR 370.42). If the generator tank is the only fuel over the line, say so in the location so responders find it.

Some states set lower thresholds. Delaware applies 55 gallons or 500 lb to hazardous chemicals but keeps 10,000 lb for fuel used only to heat buildings, according to its reporting instructions. California's hazardous materials business plan starts at 55 gallons of a liquid. Check your state page.

Diesel is not an extremely hazardous substance, so it never triggers the section 302 emergency planning notice on its own. It does bring the one-time section 311 submission of its SDS, or a chemical list, within three months of the site first going over 10,000 lb (40 CFR 370.33(a)).

Common questions

Is an emergency generator tank exempt?

No exemption in 40 CFR 370.13 covers stored generator fuel. It counts toward the 10,000 lb diesel total.

We only fill the tank twice a year. Which amount counts?

The largest amount on site on any one day, which is usually the day after a delivery.

How many gallons of diesel reach the 10,000 lb threshold?

Roughly 1,300 to 1,470 gallons. TCEQ's method multiplies gallons by the specific gravity on the safety data sheet and by 8.3, and one diesel SDS, from Vitol, lists a specific gravity of 0.82 to 0.93. Use the figure on your own fuel's SDS.

We build the battery and chemical inventory, check every threshold and file in your state's system. $950 a site per year, $750 a site from the third site. State fees extra.

Get a quote