| Key facts | |
|---|---|
| Threshold | 10,000 lb at any one time (40 CFR 370.10(a)(2)(i)) |
| Extremely hazardous substance? | No. Propane is not on 40 CFR part 355, Appendix A |
| What to add up | Every forklift cylinder, full spare and bulk tank on the peak day |
| Due | March 1, for the previous calendar year |
The threshold
Propane is not on EPA's list of extremely hazardous substances in 40 CFR part 355, Appendix A. It is a hazardous chemical with a safety data sheet, so the general Tier II threshold of 10,000 lb applies under 40 CFR 370.10(a)(2)(i). There is no separate threshold for forklift cylinders.
Add every cylinder and tank
Under 40 CFR 370.14 you look at the total quantity present throughout the facility at any one time. For propane that means:
- cylinders mounted on forklifts and other equipment
- full cylinders in the exchange cage
- cylinders that are not yet empty in the return rack
- any bulk tank used to refill cylinders or heat the building
Count on your highest day. With a cylinder exchange service, that is often delivery day, when full cylinders arrive before partly used ones leave.
| Where | Count | Propane each | Total |
|---|---|---|---|
| Cylinders on forklifts | 18 | 33 lb | 594 lb |
| Full cylinders in exchange cage | 42 | 33 lb | 1,386 lb |
| Total propane on site | 60 | 1,980 lb |
The sample is fictional. Use the propane capacity marked on your own cylinders and the delivery records from your supplier.
Bulk tanks
A bulk propane tank changes the picture quickly. Tank capacity is often given in gallons, so convert it to pounds with the specific gravity from the propane SDS, using the same method as TCEQ's Tier II weight converter: gallons × specific gravity × 8.3. Use the largest amount actually in the tank on any day, not the tank's rated volume, if your fill records show it.
Why propane rarely triggers a report alone
| Setup | Propane on site | Against 10,000 lb |
|---|---|---|
| 60 forklift cylinders at 33 lb (sample above) | 1,980 lb | Below |
| 150 cylinders at 33 lb | 4,950 lb | Below |
| 305 cylinders at 33 lb | 10,065 lb | At or over |
Most single buildings stay under the line on cylinders alone, but a site with a bulk tank or a very large fleet can cross it. Even below 10,000 lb, the site may still owe a Tier II report for forklift battery acid or diesel, and the propane does not need to be listed unless the state asks for it.
On the report
If propane is reportable, list it with the name and CAS number from the SDS, its hazard categories, the maximum and average daily amounts as range codes, days on site, storage type such as cylinder or above-ground tank, and where the cylinders are kept. Fire departments use the location field, so name the cage and any bulk tank (40 CFR 370.42).
The first year propane goes over the line, the section 311 duty also applies: send the propane SDS, or a list of your reportable chemicals, to the state commission, the local committee and the fire department within three months (40 CFR 370.33(a)). After that, an updated SDS is needed only when significant new information comes out.
Common questions
Do empty cylinders count?
Count the propane actually in them. A cylinder that still holds fuel counts for what it holds.
Does propane trigger the section 302 notice?