Warehouse Filings

When does a cold storage warehouse report anhydrous ammonia?

Anhydrous ammonia is an extremely hazardous substance with a threshold planning quantity of 500 lb. A refrigeration system holding 500 lb or more triggers both a Tier II report by March 1 and a one-time emergency planning notice to the state commission and local committee within 60 days.

Reviewed November 2026 ยท 8 sources listed at the end

Ammonia's numbers

Source: eCFR, current to November 19, 2026.
ItemValueRule
EPA list statusExtremely hazardous substance, CAS 7664-41-740 CFR 355, Appendix A
Threshold planning quantity500 lb40 CFR 355, Appendix A
Tier II threshold500 lb (500 lb or the TPQ, whichever is lower)40 CFR 370.10(a)(1)
Section 302 noticeWhen 500 lb or more is present, within 60 days40 CFR 355.10, 355.20
Reportable quantity for releases100 lb40 CFR 355, Appendix A

Because ammonia's threshold planning quantity equals the 500 lb Tier II minimum, a cold storage refrigeration system with 500 lb or more of ammonia owes both the yearly Tier II report and the one-time section 302 notice. Count the ammonia in the whole system: receivers, evaporators, piping and any stored cylinders. As an extremely hazardous substance, every pound on site is added together.

The refrigeration machinery room of a cold storage warehouse, with insulated piping, compressors and valves
Ammonia in the whole system counts: receivers, piping, evaporators and stored cylinders.

The section 302 notice

Under 40 CFR 355.20 a facility that first has an extremely hazardous substance at or above its threshold planning quantity must:

  • notify the state emergency response commission and the local emergency planning committee within 60 days
  • designate a facility emergency coordinator and tell the local committee within 60 days
  • tell the local committee of changes relevant to emergency planning within 30 days
  • give the local committee information it needs for the local emergency plan when it asks

The Tier II report then shows that the facility is subject to section 302 and names the emergency coordinator (40 CFR 370.42(k) and (o)). See the section 302 guide.

A cold storage case from 2025

EPA Region 5 settled with Olson Commercial Cold Storage, Ltd., in Defiance, Ohio, under docket EPCRA-05-2025-0006. According to the consent agreement, anhydrous ammonia, sulfuric acid and lead were each present at the facility at or above their thresholds during 2019 to 2022, and the company was required to submit safety data sheets or a chemical list and yearly inventory forms including each of them to the Ohio SERC, the Defiance County LEPC and the Defiance Fire Department. The civil penalty was $25,000.

The case shows how a cold storage site can owe for both: ammonia in the refrigeration system, plus sulfuric acid and lead in forklift batteries.

Other programs to check

The Tier II form asks whether the facility is subject to the Clean Air Act chemical accident prevention rules, the Risk Management Program in 40 CFR part 68 (40 CFR 370.42(l)). Ammonia refrigeration operators should confirm that status with their engineers before they file, so the flag on the Tier II form is right. A release of ammonia above its reportable quantity triggers emergency release notification under section 304, which is separate from Tier II.

The section 311 deadline in the Olson case

The Olson consent agreement also shows how the one-time SDS duty is dated. Ammonia was present above the threshold as of December 31, 2019, and EPA says the company was required to submit the SDS, or a list including ammonia, by March 31, 2020, and the inventory form for 2019 by March 1, 2020. That matches the three-month window in 40 CFR 370.33(a) and the March 1 date in 370.45.

Common questions

Do I count ammonia in the piping?

Count the ammonia in the whole system on site. As an extremely hazardous substance, every pound in every part of the system and in any stored cylinders is added together.

Is the section 302 notice yearly?

No. It is a one-time notice within 60 days of first reaching the threshold planning quantity, with updates to the local committee within 30 days of relevant changes.

What is the reportable quantity for an ammonia release?

100 lb, under 40 CFR part 355, Appendix A. The Tier II threshold and the threshold planning quantity are both 500 lb.

We build the battery and chemical inventory, check every threshold and file in your state's system. $950 a site per year, $750 a site from the third site. State fees extra.

Get a quote